Key takeaways
- NEC Table 430.248 lists 12 A for any 2 HP single-phase motor at 230 V. The wire must carry 125 percent of that, 15 A, which 14 AWG NM-B cable does exactly.
- The breaker may be anything from the maker's figure up to 250 percent of 12 A, which is 30 A. Grizzly asks for at least 15 A on its G1029Z2P and Jet for at least 20 A on its DC-1200VX.
- A single receptacle on its own circuit must be rated at least as high as the breaker. Grizzly ships a NEMA 6-15 plug, so on one 6-15 outlet the breaker is 15 A.
- 30 A on 10 gauge sits at the code's ceiling, not below it. It is legal with a 30 A receptacle or hardwiring. No maker checked asks for it.
- A 2 HP motor on 120 V is a 24 A load in the same table, double the 240 V figure. Harbor Freight's 120 V, 2 HP collector lists 14 A and ships a 15 A plug.
Two answers circulate. The usual forum answer is a 30 A breaker on 10 gauge wire, the same circuit people run for a 3 HP saw. The other is to read the label: Grizzly's G1029Z2P lists 9 A and asks for a 15 A circuit. Both are legal. Neither starts where the code starts.
The National Electrical Code (NEC) sizes a motor circuit from a table, not from the label. Below, four 2 HP collectors are set beside that table. 30 A on 10 gauge sits at the very top of the allowed band. The bottom is half that.
The terms this answer turns on
2 HP is the motor's rated output in horsepower. On a dust collector it is the impeller motor, the only real load on the circuit.
The breaker is the double-pole breaker in the panel. It opens both hot wires of a 240 V circuit. On a motor circuit its job is to stop a short circuit or a ground fault. It does not protect the motor from running hot.
Nameplate amps are the current printed on the motor or in the manual. Grizzly calls it the "Full-Load Current Rating". It defines that as the current the machine draws "at 100% of the rated output power."
Table current is the figure NEC Table 430.248 gives every single-phase motor of a given horsepower and voltage. The code calls it full-load current, or FLC. It is the same for every brand.
Ampacity is the current a wire can carry all the time without overheating. It depends on the wire size and on its insulation's temperature rating.
Which current sizes the circuit? Open Exam Prep's guide to Article 430 is blunt: table current "MUST be used for sizing conductors, switches, and short-circuit/ground-fault protection." The nameplate is used "ONLY for sizing motor overload protection." So the wire and the breaker come from the table.
Worked through: Grizzly's G1029Z2P on 240 V
Take the Grizzly G1029Z2P, a 2 HP bag collector rated at 1550 CFM. Its manual lists 240 V single phase, a full-load current of 9 A and a minimum circuit size of 15 A. It ships with a 6 ft, 14 AWG cord and a NEMA 6-15 plug.
Step one, the table current. Table 430.248 gives 12 A for a 2 HP motor at 230 V. The circuit uses 12 A, not the 9 A on the label.
Step two, the wire. Section 430.22 sizes the wire at 125 percent of the table current:
12 A x 1.25 = 15 A
Cerrowire rates 14 AWG copper NM-B at 15 A. It passes, with nothing to spare. Mike Holt's EC&M article works this exact motor, a 2 hp, 230 V single-phase unit, and gets the same 15 A. Holt reads the 75 C column, where 14 AWG is 20 A.
Step three, the breaker ceiling. Table 430.52 allows an ordinary panel breaker, the inverse time kind, up to 250 percent of the table current:
12 A x 2.50 = 30 A
30 A is a standard size under 240.6(A), so no rounding is needed. Holt's example reaches the same 30 A.
Step four, the floor. Grizzly asks for at least 15 A. If the circuit is fused, it wants "a time delay fuse marked D."
Step five, the outlet. Section 210.21(B)(1) says "A single receptacle installed on an individual branch circuit shall have an ampere rating not less than that of the branch circuit." The plug Grizzly ships is a 6-15. One 6-15 outlet on its own circuit means a breaker of 15 A at most.
So, as shipped and plugged into one outlet, the G1029Z2P goes on a 15 A double-pole breaker and 14 AWG or larger wire, exactly what Grizzly asks for. Up to 30 A is allowed only with a 30 A outlet or with the collector wired in directly.
Four 2 HP collectors, one table
Every 2 HP, single-phase collector checked for this page, with the maker's own figures beside the code arithmetic:
| Collector | Listed current | At | Maker's circuit figure | Plug | Table 430.248 | Wire must carry, table x 1.25 | Nameplate x 1.25 |
|---|---|---|---|---|---|---|---|
| Grizzly G1029Z2P | 9 A | 240 V | 15 A minimum circuit | NEMA 6-15 | 12 A | 15 A | 11.25 A |
| JET DC-1200VX | 8 A | 230 V | breaker, plug and outlet at least 20 A | none supplied | 12 A | 15 A | 10 A |
| Laguna P-Flux 2 | 14 A | 220 V | not stated | none supplied | 12 A | 15 A | 17.5 A |
| Harbor Freight 59726 | 14 A | 120 V | nominal 120 V circuit | plug for up to 15 A | 24 A | 30 A | 17.5 A |
The labels run from 8 to 14 A for the same 2 HP at 240 V. Grizzly and Jet sit below the table's 12 A. Laguna sits above it.
The Laguna row is the one to read twice. On the table, the wire must carry 15 A, and 14 AWG NM-B passes. On Laguna's own 14 A, 14 x 1.25 = 17.5 A, and 14 AWG NM-B fails. That case is worked below.
The Harbor Freight row is a different machine: a 2 HP motor built for 120 V. It has its own section.
The wire: 125 percent of 12 A
Cerrowire's chart, based on the 2017 NEC with no corrections applied, lists copper by insulation temperature:
| Copper | 60 C (NM-B, UF-B) | 75 C (THW, THWN, XHHW) | 90 C (THHN, THWN-2) | 15 A, table | 17.5 A, Laguna label |
|---|---|---|---|---|---|
| 14 AWG | 15 A | 20 A | 25 A | Passes, exactly in NM-B | Fails in NM-B; passes at 75 C |
| 12 AWG | 20 A | 25 A | 30 A | Passes | Passes |
| 10 AWG | 30 A | 35 A | 40 A | Passes | Passes |
NM-B is the sheathed cable in most garage walls, and Cerrowire lists it only in the 60 C column. So in NM-B, the code minimum for a 2 HP collector at 240 V is 14 AWG.
14 AWG has no margin on the table figure, and it falls short of Laguna's label. 12 AWG NM-B, at 20 A, clears both readings for every 240 V collector in the table.
Is 14 AWG on a 30 A breaker really allowed? On a motor circuit, yes. The breaker guards against shorts, not overload. Holt's guide to the 2020 code says readers may be "uncomfortable" with Article 430's allowances, "such as protecting a 10 AWG conductor with a 60A overcurrent protective device." His 2 hp example puts 14 AWG on a 30 A breaker.
The breaker band: maker's floor to the code's ceiling
The ceiling is Table 430.52. Open Exam Prep lists 250 percent for an inverse time breaker on a single-phase motor, and 175 percent for a dual-element time-delay fuse. Where the result is not a standard size, the next standard size up is allowed. The standard sizes in 240.6(A) run 15, 20, 25, 30, 35 A and up.
| Protection | Arithmetic | Largest allowed |
|---|---|---|
| Inverse time breaker, 250 percent | 12 x 2.50 = 30 | 30 A |
| Time-delay fuse, 175 percent | 12 x 1.75 = 21, next size up | 25 A |
The floor is the motor's start. Holt says the device must be "capable of carrying the motor's starting current." His 2020 code guide puts start-up current at "typically six (or more) times the running current." No code table gives a collector's starting figure, so the makers set the floor. Grizzly says 15 A. Jet says "at least a 20 amp circuit breaker or fuse."
So the band is 15 to 30 A for the Grizzly and 20 to 30 A for the Jet. Laguna's page gives no circuit figure, and on the table its ceiling is the same 30 A.
Why may the breaker be so much larger than the running current? Because a separate device handles overload. Section 430.32, in Holt's words, wants it set to open at no more than "115% of the motor nameplate FLC rating" for a continuous duty motor over 1 hp. For the G1029Z2P that is 9 A x 1.15 = 10.35 A. That is where the label is used.
When the label outranks the table
The code has an exception, and it decides the Laguna row. 430.6(A)(1) Exception No. 3, in the 2008 text on Solar365, reads: "For a listed motor-operated appliance that is marked with both motor horsepower and full-load current, the motor full-load current marked on the name-plate of the appliance shall be used instead of the horsepower rating."
Where it applies, the nameplate sizes the wire and the breaker, not the table. For Grizzly and Jet that makes the circuit smaller than the table's. For Laguna it makes it larger: 14 A x 1.25 = 17.5 A, and the breaker ceiling becomes 14 x 2.50 = 35 A.
Whether a collector counts as a listed motor-operated appliance is the inspector's call. The manuals and the product page read here do not say. 12 AWG NM-B passes on either reading for all three 240 V units.
Is "30 A on 10 gauge" right?
It is legal, and it is the largest circuit the motor rules allow. 10 AWG NM-B, at 30 A, carries far more than the 15 A the wire needs. 30 A is exactly 250 percent of 12 A.
What the rule leaves out is the outlet. With one receptacle on the circuit, that receptacle must be a 30 A, NEMA 6-30. Grizzly ships a 6-15 plug, and Jet asks only for a plug and outlet rated "at least 20 amps." So 30 A means a 30 A outlet and a plug to match, or wiring the collector in directly. The cord itself is a separate question, covered under limits below.
The rule persists because it is the 3 HP answer. A 3 HP motor is 17 A in the same table and needs wire for 21.25 A, which is 10 AWG in NM-B, as worked in the 3 HP table saw breaker and wire guide. For a 2 HP collector, the same circuit is double the wire the code asks for.
The folk source: "10 gauge for 40 A intermittent"
The usual citation for oversized dust collector circuits is Bill Pentz's electrical page. Pentz writes that "10-gauge wire is rated for ongoing current loads up to 30 amps, or 40 amps if you are running intermittently loaded motors such as on a table saw or joiner." He recommends wiring a shop with "multiple 240V dedicated circuits."
His 30 A figure matches Cerrowire's 60 C column for 10 AWG. The 40 A figure does not appear in that column. Cerrowire's 40 A for 10 AWG is the 90 C column, the one for single wires such as THHN, not NM-B. Pentz also ties it to intermittent loads like a saw. A collector is the opposite case. Jet's manual notes that "dust collectors are generally used at the same time other tools are running."
For a 2 HP collector, the folk figure is beside the point anyway. A 40 A breaker would be over the 30 A ceiling of Table 430.52.
The 120 V case
A 2 HP motor on 115 V is 24 A in Table 430.248, double the 230 V figure. Same motor, same power, half the voltage, twice the current.
| On the table | 230 V | 115 V |
|---|---|---|
| 2 HP table current | 12 A | 24 A |
| Wire must carry, x 1.25 | 15 A | 30 A |
| Breaker ceiling, x 2.50 | 30 A | 60 A |
On the table, a 120 V, 2 HP motor needs wire for 30 A, which is 10 AWG NM-B.
Harbor Freight sells one. Its item 59726 manual lists "120VAC / 60Hz / 14A" and "2HP, Single Phase". It is "for use on a nominal 120-V circuit" with a plug rated "for up to 125 VAC and up to 15 A." The label reads 14 A against the table's 24 A, 58 percent of it, which is the widest gap of the four collectors here.
Two circuit rules then apply to a plug-in tool on 120 V:
- The 80 percent cap. Section 210.23 limits one cord-and-plug load on a circuit with other outlets to 80 percent of the breaker: 12 A on 15 A, 16 A on 20 A. The 14 A collector is over the cap on 15 A and under it on 20 A.
- The outlet. Section 210.21(B)(3) allows 15 A receptacles on a 20 A circuit that has two or more receptacles. So the 15 A plug can go on a 20 A circuit.
That makes a 20 A circuit the fit for this collector. On the nameplate reading, under Exception No. 3, the wire must carry 14 x 1.25 = 17.5 A, so 12 AWG NM-B. On the table reading it must carry 30 A, so 10 AWG. As with Laguna, which applies depends on the listing.
A 15 A circuit shared with a saw is out of the question. The table saw and dust collector circuit guide sums those loads at 21 to 28 A.
Dual voltage: what rewiring changes
None of the four 2 HP collectors read here is dual voltage. Grizzly, Jet and Laguna list 230 or 240 V only, and Harbor Freight lists 120 V only.
Grizzly's 1.5 HP G1028Z2, in the same manual, shows how a dual voltage unit works. It lists 12 A at 120 V and 6 A at 240 V, and a 15 A circuit at either voltage. It ships prewired for 120 V with a 5-15 plug. Converting it means rewiring the motor in its junction box and fitting a 6-15 plug. Grizzly says the conversion "MUST be performed by an electrician or qualified service personnel."
The table shows the same halving for 1.5 HP: 20 A at 115 V, 10 A at 230 V.
The answer, collector by collector
Each row restates a ruling made above:
| Collector | Breaker | Wire, NM-B | Outlet |
|---|---|---|---|
| Grizzly G1029Z2P, as shipped | 15 A double-pole | 14 AWG minimum, 12 AWG for margin | single 6-15 |
| JET DC-1200VX | 20 to 30 A double-pole | 14 AWG minimum, 12 AWG for margin | rated at least as high as the breaker, and at least 20 A |
| Laguna P-Flux 2 | up to 30 A on the table, no maker floor | 12 AWG, which passes the 14 A label | rated at least as high as the breaker |
| Harbor Freight 59726, 120 V | 20 A | 12 AWG if the label governs, 10 AWG on the table | 15 A receptacle on a circuit with two or more |
Where this answer stops applying
- Three-phase collectors. They use Table 430.250, not 430.248. Jet's three-phase DC-1200VX lists 6 A at 230 V. Nothing on this page applies to it.
- The cord and the plug. Holt notes that flexible cord is sized under 400.5, a different rule. Grizzly and Jet ship a 14 AWG cord. This page does not rule on fitting a 30 A plug to it.
- Hot or bundled runs. Cerrowire's figures carry no temperature correction or adjustment. A run through a hot attic, or bundled with other circuits, can need larger wire.
- The 75 C column. It counts only where the wire type, the breaker and the terminals are all rated for it.
- A breaker above the maker's figure. The band up to 30 A assumes the overload device required by 430.32 is there. If the manual does not show one, ask the maker before going above its circuit figure.
- Laguna's floor. Laguna's page gives no minimum circuit, so no figure here says how small a breaker its motor will start on.
- Local codes. Everything here is the NEC as published, and local amendments win. Grizzly and Jet both want an electrician to do the wiring.
- Published figures only. Every current comes from the makers' manuals and pages. No collector was wired or measured for this page.
Planning the outlets
A collector runs while a saw does. Grizzly's circuit figures assume a dedicated circuit, and Jet says one "will give you the best results." So each machine gets its own. The same table method sizes the other big 240 V motor in many shops, the compressor, in the 60 gallon compressor breaker guide. Place both outlets before a wall system goes up, as the garage shop layout guide advises. If a collector has to reach a far corner on a cord, the extension cord gauge guide covers the voltage drop. Harbor Freight's own cord table puts a 12.1 to 16 A tool on 12 gauge at 50 ft.
The thirty-second check
- Read the horsepower and the voltage on the motor. For 2 HP, the table says 12 A at 230 V and 24 A at 115 V.
- Wire for 125 percent of that: 15 A at 240 V, so 14 AWG NM-B at minimum. Use 12 AWG if the label is above 12 A.
- Pick a breaker from the maker's minimum up to 30 A at 240 V.
- Match the outlet. One receptacle on the circuit must be rated at least as high as the breaker. A 6-15 means 15 A.
- Treat 30 A on 10 gauge as the ceiling, not the starting point.