Key takeaways
- Gallons never enter the arithmetic. Grizzly sells a 3 HP and a 5 HP compressor on the same 60 gallon tank, and asks for a 20 A circuit on one and 30 A on the other.
- NEC Table 430.248 lists 17 A for a 3 HP single-phase motor at 230 V and 28 A for 5 HP. The wire must carry 125 percent of that, 21.25 A for 3 HP and 35 A for 5 HP.
- 10 AWG NM-B cable is rated 30 A. It passes for 3 HP and fails for 5 HP by 5 A. 8 AWG NM-B, rated 40 A, passes both.
- An ordinary panel breaker may be up to 250 percent of the table current, 45 A for 3 HP and 70 A for 5 HP. The makers' own minimums, 20 to 30 A, sit at the bottom of that band.
- "30 A for a 60 gallon" holds for the 3 to 3.7 HP class on 10 AWG. On a true 5 HP the 30 A breaker is fine and the 10 gauge wire is not.
Two answers circulate. One says every 60 gallon compressor gets a 30 A breaker on 10 gauge wire. The other says to read the label and match it. Neither starts where the code starts. The National Electrical Code (NEC) sizes a motor circuit from the motor's horsepower, read off a table. The tank is not in the arithmetic at all.
Below, five 60 gallon compressors are set beside that table. The 30 A rule turns out to be right for one class of motor and wrong for the other, and the part it gets wrong is the wire.
The terms this answer turns on
The breaker here is a double-pole breaker in the panel, which opens both hot wires of a 240 V circuit. Its job on a motor circuit is to stop a short circuit or a ground fault. It is not what protects the motor from running hot.
Nameplate amps are the current printed on the motor or the spec sheet. Grizzly calls it "Full-Load Current Rating".
Table current is the current NEC Table 430.248 lists for every single-phase motor of a given horsepower and voltage. The code calls it full-load current, or FLC. It is a fixed figure, the same for every brand.
Ampacity is how much current a wire can carry all the time without overheating. It depends on the wire size and on the temperature rating of its insulation.
An overload device is a separate part that trips when the motor draws too much for too long. It is sized from the nameplate, not the table.
Which current sizes the circuit? Open Exam Prep's guide to Article 430 puts it plainly: the table current "MUST be used for sizing conductors, switches, and short-circuit/ground-fault protection." The nameplate is for "sizing separate motor overload protection devices." So the wire and the breaker come from the table.
Worked through: a 5 HP, 60 gallon Grizzly
Take Grizzly's G0955. Its spec sheet lists a 5 HP single-phase motor at 230 V, a "Full-Load Current Rating" of 22.5 A, and a "Minimum Circuit Size" of 30 A. It is listed for permanent connection, "Hardwire to Shutoff Switch".
Step one is the table current. Table 430.248 gives 28 A for a 5 HP motor at 230 V. That is the number the circuit uses, not the 22.5 A on the sheet.
Step two is the wire. Holt's summary of section 430.22 says to size conductors at "at least 125% of the motor FLC":
28 A x 1.25 = 35 A
Cerrowire rates 10 AWG copper NM-B at 30 A. That is 5 A short. 8 AWG NM-B is 40 A and passes.
Step three is the breaker ceiling. Table 430.52 allows an inverse time breaker, the ordinary panel kind, up to 250 percent of the table current:
28 A x 2.50 = 70 A
70 A is a standard size under 240.6(A), so it needs no rounding.
Step four is the floor. Grizzly asks for at least 30 A.
So this compressor can sit on any breaker from 30 to 70 A, and the wire must be good for 35 A whatever the breaker. A 30 A breaker on 10/2 NM-B fails, and only because of the wire.
Now read the label instead of the table and see where the folk rule comes from. 22.5 A x 1.25 = 28.1 A, and 10 AWG NM-B at 30 A clears that. On the nameplate reading the popular answer passes. On the code's reading it does not.
Why gallons do not set the circuit
Grizzly makes the point with its own range. The G0954 and G0955 both use a 60 gallon tank. The G0954 has a 3 HP motor at 15 A and asks for a 20 A minimum circuit. The G0955 has a 5 HP motor at 22.5 A and asks for 30 A.
Same tank, two circuits. The motor is the load, and the tank is storage. A bigger tank does not raise the pump's output either, as worked through in whether a bigger compressor tank gives more CFM. Air delivery follows the pump too: 10.2 CFM at 90 psi for the 3 HP Grizzly against 18 SCFM for the 5 HP.
So "60 gallon" names a tank that is sold with 3 HP, 3.2 HP, 3.7 HP and 5 HP motors. Read the motor line before anything else.
Five 60 gallon compressors, one table
Every 60 gallon, single-phase compressor checked for this page, with the maker's own figures beside the code arithmetic:
| Compressor | HP | Listed current | Maker's circuit or wire figure | Table 430.248 at 230 V | Wire must carry (x 1.25) | Breaker band |
|---|---|---|---|---|---|---|
| Grizzly G0954 | 3 | 15 A at 240 V | 20 A minimum circuit, hardwired | 17 A | 21.25 A | 20 to 45 A |
| Husky VT631404 | 3.2 | 15 A at 230/240 V | 10 AWG up to 75 ft; type T fuses or double-pole breaker | no row (between 17 and 28 A) | 21.25 or 35 A | 15 A up to 45 or 70 A |
| Campbell Hausfeld XC602100 | 3.7 | 17.2 A at 230 V | dedicated 240 V supply, no cord supplied | no row (between 17 and 28 A) | 21.25 or 35 A | not stated, up to 45 or 70 A |
| Grizzly G0955 | 5 | 22.5 A at 230 V | 30 A minimum circuit, hardwired | 28 A | 35 A | 30 to 70 A |
| TMG-ACE60 | 5 | 25 A at 230 V | 25 A minimum circuit, NEMA 6-30R | 28 A | 35 A | 25 to 30 A with its 6-30R |
The bottom of each band is the maker's figure. Husky gives no breaker size, but its manual says the wiring "and protector must be rated for at least the amperage and voltage indicated on the motor nameplate", which is 15 A. The top is the 250 percent ceiling worked below. TMG prints its 25 A under "Power Requirements", beside the receptacle, rather than as a motor rating. The TMG row is capped at 30 A by that receptacle, for the reason in the section on plugs.
The 3.2 and 3.7 HP rows have no table row of their own. They are worked in their own section.
The wire: 125 percent of the table current
Holt's worked example in EC&M uses a 2 hp motor: 12A x 1.25 = 15A. The same step for the two table rows that matter here:
- 3 HP:
17 A x 1.25 = 21.25 A - 5 HP:
28 A x 1.25 = 35 A
Cerrowire's ampacity chart, based on the 2017 NEC with no corrections applied, lists copper by insulation temperature:
| Copper | 60 C (NM-B, UF-B) | 75 C (THW, THWN, XHHW) | 3 HP, 21.25 A | 5 HP, 35 A |
|---|---|---|---|---|
| 12 AWG | 20 A | 25 A | Fails in NM-B; passes at 75 C | Fails |
| 10 AWG | 30 A | 35 A | Passes | Fails in NM-B; meets it exactly at 75 C |
| 8 AWG | 40 A | 50 A | Passes | Passes |
| 6 AWG | 55 A | 65 A | Passes | Passes |
NM-B is the sheathed cable in most garage walls, and Cerrowire lists it only in the 60 C column. So in NM-B, a 3 HP compressor needs 10 AWG and a 5 HP needs 8 AWG.
The 75 C column is for single wires such as THWN, usually pulled in conduit. There, 12 AWG clears 3 HP and 10 AWG meets 5 HP's 35 A exactly. Husky's own figure, 10 AWG for runs up to 75 ft, fits a 3 HP class motor in either column.
The breaker band: maker's floor to the code's ceiling
The ceiling is Table 430.52. It allows an inverse time breaker up to 250 percent of the table current, and a dual-element time-delay fuse up to 175 percent. Where the result is not a standard size, the next standard size up is allowed. The standard sizes in 240.6(A) run 15, 20, 25, 30, 35, 40, 45, 50, 60, 70 A and up.
| Motor | Breaker, 250 percent | Time-delay fuse, 175 percent |
|---|---|---|
| 3 HP, 17 A | 17 x 2.50 = 42.5, so 45 A | 17 x 1.75 = 29.75, so 30 A |
| 5 HP, 28 A | 28 x 2.50 = 70 A | 28 x 1.75 = 49, so 50 A |
The floor is the start. A motor draws far more for a moment when it starts. Holt notes locked-rotor current can reach "six times the full-load ampere rating." TMG's manual makes the same point: "the momentary starting current of an electric motor is greater than its full load current," so "Time-delay or 'slow- blow' circuit breakers are recommended." Husky names "slow blow fuses type T" or a 240 V double-pole breaker. No code table gives the starting figure, so the makers' minimums set the floor.
Why may the breaker be so much larger than the motor's running current? Because the breaker is not the overload protection. Section 430.32, in Holt's words, needs an overload device for a continuous duty motor over 1 hp "sized to open at no more than 115% of the motor nameplate FLC rating", or 125 percent with a service factor of 1.15 or more. For the G0955 that is 22.5 x 1.15 = 25.9 A. That is where the nameplate is used.
Grizzly lists a "Pressure Switch w/Motor Reset Button" on both its 60 gallon units. TMG's troubleshooting chart reads "Circuit breaker on motor tripped. Push button located on back of motor."
The 3.2 and 3.7 HP problem
Table 430.248 jumps from 3 HP to 5 HP. Nothing sits between. Husky lists its VT631404 at 3.2 HP, and Campbell Hausfeld lists the XC602100 at 3.7 HP. Neither number has a row.
The two readings give different wire. On the 3 HP row, the wire must carry 21.25 A, and 10 AWG NM-B passes. On the 5 HP row, it must carry 35 A, and 10 AWG NM-B fails.
The code material read for this page does not say which row such a motor takes. That is a ruling for the electrician or the inspector, not for this page. Two facts help them. The XC602100's 17.2 A nameplate is already above the 3 HP row's 17 A. And 8 AWG NM-B, at 40 A, passes on either reading. If the wire is going in the wall once, 8 AWG ends the question.
Is "30 A for a 60 gallon" right?
For the 3 to 3.7 HP class, on the 3 HP row, yes. A 30 A breaker is inside the 3 HP band of maker minimum to 45 A. 10 AWG NM-B, at 30 A, carries the 21.25 A the wire needs. The rule is a legal build, and it leaves room above Grizzly's 20 A and Husky's 15 A.
For a true 5 HP, it is half right. 30 A is Grizzly's own minimum for the G0955, so the breaker is fine. The 10 gauge wire that usually comes with the rule is not, since 35 A is needed and 10 AWG NM-B is 30 A.
The rule persists for two reasons. Three of the five compressors checked here are in the 3 to 3.7 HP class, where it works. And on a 5 HP label of 22.5 A, nameplate times 1.25 gives 28.1 A, which 10 AWG NM-B clears. It is the nameplate arithmetic, which Article 430 does not use for the wire.
Hardwired or plugged in
The makers split on this, and the choice changes the breaker you can use.
- Hardwired. Both Grizzly units are listed as "Permanent (Hardwire to Shutoff Switch)". Campbell Hausfeld's XC602100 "does not include a power cord" and should go to "a dedicated power supply that is 240-Volt".
- Plugged in. TMG lists "Dedicated NEMA Receptacles 6-30R" for the 5 HP ACE60. Husky allows permanent wiring to the pressure switch, or "A properly sized cord with a ground conductor and plug may also be installed by the user."
A receptacle caps the breaker. Section 210.21(B)(1): "A single receptacle installed on an individual branch circuit shall have an ampere rating not less than that of the branch circuit." A 6-30R is rated 30 A, so the breaker on it can be no more than 30 A. For the TMG that leaves a band of 25 to 30 A, with the wire still sized for 35 A.
The same rule applies to the 3 HP saw circuit in the 3 HP table saw breaker and wire guide, which uses the same table and the same steps. A welder is the other big 240 V load in many shops, and it follows a different article of the code, as the Lincoln AC225 breaker guide shows.
Long runs and low voltage
Starting current is what punishes a long, thin run. TMG says "Power leads must be adequately sized to protect against excessive voltage drop during start-up." Husky sets a length on its 10 AWG figure, "wiring used up to 75 ft. long must be 10 AWG", and gives no figure past that.
Both makers also rule out 208 V. Husky's troubleshooting chart says "The motor will not run properly on 208 volts," and blames low voltage on wires "too small in diameter and / or too long." TMG says "Do not use this unit on a 208V circuit of any kind" and wants at least 208 V at the terminal.
Both makers also say the circuit is for the compressor alone. Husky's answer to a breaker that trips repeatedly includes "Limit the circuit to the use of only the air compressor."
Where this answer stops applying
- Three-phase compressors. They use NEC Table 430.250, not 430.248. Nothing on this page applies to them.
- Hot or bundled runs. Cerrowire's figures carry no temperature correction or adjustment. A run through a hot attic, or bundled with other circuits, can need larger wire.
- The 75 C column. It counts only where the wire type is listed in it and the breaker and terminals are rated for it. Check the markings before relying on 10 AWG at 35 A.
- Breakers above the maker's figure. The band up to 45 or 70 A assumes the motor has overload protection under 430.32. Where the maker does not show it, ask the maker before going above its circuit figure.
- Runs past the maker's length. Husky's 10 AWG stops at 75 ft. Past that, the wire may need to grow for voltage drop at start, and no source here gives the size.
- Local codes. Everything here is the NEC as published. Local amendments win. Husky and TMG both want a qualified electrician to do the wiring.
- Published figures only. Every nameplate and circuit figure comes from the makers' sheets and manuals. No compressor was wired or measured for this page.
Placing the compressor and its air
A 60 gallon compressor stands in the floor zone, and the garage shop layout guide advises planning its dedicated circuit before a wall system goes up. The air side has its own sizing problem. The air hose guide for impact wrenches covers the pressure a long hose loses between the tank and the tool.
The thirty-second check
- Read the motor's horsepower and voltage. Ignore the tank size.
- Look up the table current: 17 A for 3 HP, 28 A for 5 HP, at 230 V single phase.
- Wire for 125 percent of it: 21.25 A (10 AWG NM-B) or 35 A (8 AWG NM-B). For 3.2 or 3.7 HP, 8 AWG passes on either row.
- Pick a breaker from the maker's minimum up to 45 A (3 HP) or 70 A (5 HP).
- If it plugs in, the receptacle must be rated at least as high as the breaker. A 6-30R means 30 A at most.